ࡱ> MOL_ v.bjbjzyzy GC6b6bV% 00000DDD8|$,D-6(!# y-{-{-{-{-{-{-$0/18-0$$$-00-((($00y-($y-((++t/%^+e--0-+,3%3+30+t$$($$$$$--'$$$-$$$$3$$$$$$$$$ B : SECTION 25 11 09 - BAS operator interfaces GENERAL RELATED DOCUMENTS Drawings and general provisions of the Contract, including General Conditions and Division01 Specification Sections, apply to this Section. SUMMARY Includes: Operator Workstations. Control System Servers. Portable Operator Terminal / Remote Workstation. Furnish and install all Operator Interfaces and Control System Servers as required for the BAS functions specified. All computers shall be warranted by the manufacturer for a period of one year after final acceptance. REFERENCE STANDARDS The latest published edition (prior to the contract date) of a reference shall be applicable to this Project unless identified by a specific edition date. All reference amendments adopted prior to the effective date of this Contract shall be applicable to this Project. All materials, installation and workmanship shall comply with the applicable requirements and standards addressed within the following references: PRODUCTS GENERAL All materials shall meet or exceed all applicable referenced standards, federal, state and local requirements, and conform to codes and ordinances of authorities having jurisdiction. The make and model of control system server computers, personal computers (PC), notebook PCs, and monitors shall comply with Owners current standards for desktop personal computers as of the date of Substantial Completion. Contact Owner for the current computer hardware standards. Operating system for operator workstation shall comply with Owners current standards for desktop personal computers as of the date of Substantial Completion. Contact Owner for the current computer hardware standards. OPERATOR WORKSTATION (OWS) Provide personal computer (PC) that meets or exceeds the minimum requirements of the BAS software and meets or exceeds the minimum requirements of MD ANDERSON. PC shall contain a 48x/24x/48x\16x CD-RW/DVD ROM Combo Drive. Provide 19-inch (17.9 inch viewable, 0.25-0.25AG) monitor. Provide detachable keyboard with standard typewriter layout, function keys, and separate numeric keypad. Provide a USB mouse and mouse pad with the system. Provide one open serial port after configuration of the workstation to meet the requirements of the rest of these Specifications. Workstation PC shall have the capability of changing serial port interrupt vectors and IOBASE addresses through software. Operating system for operator workstation shall meet or exceed the minimum requirements of the BAS software and shall meet or exceed the minimum requirements of MD ANDERSON. All software shall be at least the latest version available as of the date of Contract completion. Provide software, graphics and programming as specified in Section 25 15 00. Provide network card approved by BAS manufacturer to support Supervisory LAN communications (10/100/1000 Mbps Ethernet TCP/IP) for OWSs connected to the Local Supervisory LAN and network card or LANID where connected to the Primary Controller LAN. Provide additional hardware, video drivers, serial port, etc., to facilitate all control functions and software requirements specified for the BAS. It is important that the control system server and OWSs be indicated on the Drawings and/or their location clearly defined. Edit the following as applicable. Operator Workstations shall be placed as indicated on the Drawings or as directed by Owner. Control System Server (CSS) Verify with Owner if a CSS exists for use on this Project. Provide server computer that meets or exceeds the minimum requirements of the BAS software and meets or exceeds the minimum requirements of MD ANDERSON. Provide 19 inch (17.9 inch viewable, 0.25-0.25AG) Monitor if the CSS also serves as an OWS. Otherwise, a 17 inch monitor is acceptable. Provide detachable keyboard with standard typewriter layout, function keys, and separate numeric keypad. Provide an optical mouse and mouse pad with the system. Provide one open serial port after configuration of the workstation to meet the requirements of the rest of these Specifications. Workstation PC shall have the capability of changing serial port interrupt vectors and IOBASE addresses through software. Provide an uninterruptible power supply system (UPS) providing battery backup for each operator workstation and peripheral devices. UPS shall protect against blackouts, brownouts, surges and noise. UPS shall include LAN port and modem line surge protection. UPS shall be sized for a 7-minute full load runtime, 23-minute load runtime, with a typical runtime of up to 60 minutes. Transfer time shall be 2-4 milliseconds. UPS shall provide a 480-joule suppression rating and current suppression protection for 36,000 amps and provide 90 percent recharge capability in two to four hours. Suppression response time shall be instantaneous. UPS low voltage switching shall occur when supply voltage is less than 94 volts. UPS shall be provided with modem surge suppression and LAN port connections. Provide all software, cables, peripherals etc. for a complete system. Operating system for operator workstation shall meet or exceed the minimum requirements of the BAS software and shall meet or exceed the minimum requirements of MD ANDERSON. All software shall be at least the latest version available as of the date of Contract completion. Provide network configuration tool, all programming applications, graphic creation tools and all other software required to configure and operate the system. For CSSs that provide web services for presentation of data across the UTMD ANDERSON Intranet, all Web components and services shall be installed with required licensing. CSS shall be configured to secure it to the extent practical inside the Local Supervisory LAN. CSS shall always function from behind a firewall provided either by the network administrators in the case where they provide the LAN infrastructure, or by this Contractor where the LAN is provided under this Division of the Specifications. Provide network card approved by BAS Provider to support Supervisory LAN communications (10/100/1000 Mbps Ethernet TCP/IP) Provide additional hardware, video drivers, etc., to facilitate all control functions and software requirements specified for the BAS. It is important that the control system server and OWSs be indicated on the Drawings and/or their location clearly defined. Edit the following as applicable. Control System Server shall be as indicated on the Drawings or as directed by Owner: PORTABLE OPERATOR TERMINAL (POT) / REMOTE WORKSTATION Portable Operator Terminal shall support system management by connection to the controllers, by connection via the Internet, and by dial-up communications while serving as the remote workstation. Provide one notebook personal computer (PC) that meets or exceeds the minimum requirements of the BAS software and meets or exceeds the minimum requirements of MD ANDERSON. Notebook PC shall contain a 24X/24X/24X/8X CD-RW/DVD ROM Combo Drive. Provide a 10/100 LAN+56K CardBus Type III PC Card if internal adapter is not present. Provide minimum 14.1 inch XGA active matrix display. Provide carrying case and extra battery. Provide software, graphics and programming as specified in Section 25 15 00. Provide additional hardware, video drivers, serial ports, etc., to facilitate all control functions and software requirements specified for the building automation system. Provide all controller configuration and interface software and/or plug ins for all devices applicable. All shall be loaded and functional. Provide all required interface cables required to connect to all networks, routers, controllers, SDs etc. Wherever a POT connection point is not accessible in the same room as the device controlled, Contractor shall coordinate with MD Anderson IT to provide a wireless system, to permit configuration, testing and operation. Include licensing for all software packages. BAS licensing for this POT shall allow unlimited access to all aspects of the any manufacturers system including system access, workstations, points, programming, database management, graphics etc. No restrictions shall be placed on the license. All operator interface, programming environment, networking, database management and any other software used by the Contractor to install the system or needed to operate the system to its full capabilities shall be licensed and provided to the Owner. EXECUTION INSTALLATION Installation shall meet or exceed all applicable federal, state and local requirements, referenced standards and conform to codes and ordinances of authorities having jurisdiction. All installation shall be in accordance with manufacturers published recommendations. Set up workstations as indicated on the Drawings. Install all software and verify that the systems are fully operational. Ensure licensing is provided for all software. No license, software component, key, etc or any piece of information required for installing, configuring, operating, diagnosing and maintaining the system shall be withheld from the Owner. Install electronic control system Operation and Maintenance Manuals, programming guides, network configuration tools, and control Shop Drawings etc. on each OWS and CSS. Provide interface or shortcuts to guide user to the appropriate information. Set up portable operator terminal and configure it as the remote workstation. Install all software and verify that the system is fully operational. END OF SECTION 25 11 09   MD ANDERSON Project No. XX-XXXX MD ANDERSON PROJECT NAME A/E Name Issue Description A/E Project No. Month, 00, 0000 鶹ӳ BAS OPERATOR INTERFACES MD Anderson Cancer Center 25 11 09 MS20190301  PAGE 1 OF  NUMPAGES 5 *4FGO  F G   # 7 8 T q  " ( G  NYۿͿͿͿͿ۴ۿۿۿۭ h hW hGNhGN h hW h ha4 h hK$ h h h hhGN h hGN h h|8 h h;" h h, h hz h h.(q h 6hzh|8h;~hzh"M5+4G H # 8 H qgd gd gd gd;~YZmv,/27[t5=PUVW:EVXac<=z{!"ļĸļĸĴ h h1o h ha4hVCh.(qh^Aha4hGN h hZf h h^A h hW h h.(q h h h h  h hGN h h!cA[WsIs={" 4!!!"x#gd $gd gd  gd gd BM 4!g!o!!!!!$#/###o$w${&&&&''('''"(#((()))*)7)8)F*n*v*++',+,3,@,>-U-V-μμ h h) h hzhz h hd h h1ohGNha4 h hZf h ha4 h h.(q h hW h h!c h hGNBx##$,$y$&%&&(''#()*)8))F**+,>-V-X-Y-Z-[-\-]-gd gd gd gd gd V-W-]-^-x-}----.%.@.H.I.S.T.U.[.\.].^.b.c.n.o.p.q.s.t.u.v.öݮٮäjh;~U*jh;~UjhKnh;~U*hAmHnHu*jhKnh;~Uh;~ hKnh;~hgA. h;~h;~hzh\lDjh\lDU]-_-`-a-b-c-d-e-f-g-h-i-j-l-m-n-o-p-q-s-t-u-v-w-x-y-z-{-|-}-}-------&.I.r.s.t.u.v.gd gd;~gd;~gd;~ E....()()))()000?P&P/R 8$BP/ =!"#8$% Dp!s002 0@P`p2( 0@P`p 0@P`p 0@P`p 0@P`p 0@P`p 0@P`p8XV~ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@_HmH nH sH tH @`@  NormalOJQJ_HmH sH tH ZZ , Heading 1$ <@&^ ;CJKH \^JaJ RR , Heading 2$ P 1$@&^  5;CJXX , Heading 3$ h!  1$@&^ 5;mH sH DA D ;~Default Paragraph FontViV  Table Normal :V 44 la (k (;~No List :O: ;~EOS$1$a$ 5\]P@P ,Footnote Text,Foot Title;4/4 ,PR2 Char OJQJ^J@O"@ ;~PR2$$ & F*$@&a$^JH`2H ;~0Header  $OJQJ_HmH sH tH 6/A6 ;~0 Header CharOJQJ: @R: ;~0Footer  $B1$\]6/a6 ;~0 Footer CharOJQJFOF ;~PRT $$ & F*$@&a$5;HOH ;~ART$$ & F@&a$ ;\]^J@O@ ;~PR1$$ & F*$@&a$^J>/> ,ART Char;OJQJ\]^J@@ ;~PR3$$ & F*$@&a$^J4/4 ;~PR3 Char OJQJ^J@@ ;~PR4$$ & F*$@&a$^J@@ ;~PR5$$ & F*$@&a$^J4Or4 ;~SCT *$ 5;^JLOL   SPEC NOTE x5;B*OJQJ\phPK![Content_Types].xmlN0EH-J@%ǎǢ|ș$زULTB l,3;rØJB+$G]7O٭Vc:E3v@P~Ds |w< v&B"'!YV-v.x#]-}-v.  !!t8@0(  B S  ?B _Hlk446890 _Hlk446891 _Hlk447214 _Hlk447215 _Hlk447605 _Hlk447606 _Hlk448082 _Hlk448083 _Hlk449066 _Hlk449067 _Hlk449381 _Hlk449382 _Hlk449571 _Hlk449572 _Hlk449859 _Hlk449860 _Hlk450078 _Hlk450079 _Hlk450272 _Hlk450273 _Hlk450793 _Hlk450794 _Hlk451149 _Hlk451150 _Hlk451408 _Hlk451409 _Hlk451576 _Hlk451577 _Hlk451801 _Hlk451802 _Hlk451951 _Hlk451952 _Hlk452108 _Hlk452109 _Hlk452263 _Hlk452264 _Hlk452441 _Hlk452442 _Hlk452613 _Hlk452614 _Hlk506465 _Hlk506466 _Hlk506493 _Hlk506494 _Hlk506886 _Hlk506887 _Hlk506946 _Hlk506947 _Hlk507318 _Hlk507319 _Hlk508067 _Hlk508068 _Hlk508099 _Hlk508100 _Hlk512259 _Hlk512260 _Hlk512823 _Hlk512824 _Hlk513067 _Hlk513068 _Hlk2689382 _Hlk2689383 _Hlk2689880 _Hlk2689881 _Hlk2691614 _Hlk2691615}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%}%w&  !"#$%&'()*+,-./0123456789:;<=>?@A%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%w&##V%\%]%c%d%i%j%p%q%w%x%T&^&b&q&t&w&nqV%\%]%c%d%i%j%p%q%w%x%t&w&3*+GGHH#8cZZ[[ ,,!!Z"Z"">%>%U%V%\%]%c%d%i%j%o%p%q%v%w%x%}%%%T&^&b&q&s&t&w&**GGHHTq NYZZ[[  ,,!!Z"Z">%>%U%V%V%\%]%]%c%d%i%j%p%q%w%x%}%%%T&^&b&q&s&t&w&&V$^`o(GOJQJsH tH _HhH PART -  ^`o(hH SCHEDULE  -  ^`o(hHPRODUCT DATA SHEET  -  `h^``o(hH. 8h^8`o(hH. h^`o(hH. h^`o(hH. ph^p`o(hH)  h^ `o(hH)WVj  7W$:Ch_ ta;"K$1G&O(x*,gA.a4K5 6W,6t6|8x:>UA C3=C]D\lD3K-L"MGN!c~cweZfrhTjmM2m6m_Oo.(qd|`^ke&(u;~#SW?1os^FCMVC}`e[lq+bu^A=WG},)Aggz9bV%X%@3333v&@UnknownG.[x Times New Roman5Symbol3. .Cx Arial=Arial BoldA$BCambria Math"9@)hPt'Pt'&CC%)P4C%C%2q)PHP ?"M2xx UC:\Documents and Settings\dospain\Application Data\Microsoft\Templates\CSI_STYLES.dotBAS Operator InterfacesDOSpainFitzgerald,Richard W Oh+'0D     $,4<BAS Operator InterfacesDOSpainALTERATION OF THIS OFFICIAL DOCUMENT IS PROHIBITED WITHOUT EXPRESS WRITTEN PERMISSION BY OFFICE OF CAPITAL PLANNING AND MANAGEMENT AT UT MD ANDERSON CANCER CENTER. CSI_STYLESFitzgerald,Richard W2Microsoft Office Word@@V<_@@ CSI Division SZWXXFYDWACR-487-845%04327dde-80a2-4a24-9403-5f53b6f0bbc9thttp://fm/groups/cpm/TRG/odgCollmentManagement.Internal.DocIdHandler/metadata/longProperties"/> <  !#$%&'()*+,-./0123456789:;=>?@ABCeGHIJKSNQkRETUVWXYZ[\]^_`abcdlmnopDRoot Entry F`{7P1Table".3WordDocumentGCSummaryInformation(<DocumentSummaryInformation8,@CompObjrMsoDataStore `{7`{7OBXDEOCAUGFNACZFA==2`{7`{7  !"#$%&'()*+<-./0123456789:;B=?@ACDEF  F Microsoft Word 97-2003 Document MSWordDocWord.Document.89q Item  Fx.PropertiesVO5YEWLMBV4EA==2 `{7`{7Item  PropertiesKTPEEB4TII==2`{7`{7Item  Properties/xsd:simpleType> This value indicates the number of saves or revisions. The application is responsible for updating this value after each revision. 0"> ds:itemID="{3CF9A484-E94D-4DA0-8179-3AFD231D2622}" xmlDocumentLibraryFormDocumentLibraryFormDocumentLibraryForm">Document ID Generat Token=71e9bce111e9429cMicrosoft.OfficDocument ID GeneratorSynchronous100011000Microsoft.Office.DocumentManagement, Version=14.0.0.0, Culture=neutral, PublicKeyToken=71e9bce111e9429cMicrosoft.Office.DocumentManagement.Internal.DocIdHandlerDocument ID GeneratorSynchronous100021001Microsoft.Office.DocumentManagement, Version=14.0.0.0, Culture=neutral, PublicKeyToken=71e9bce111e9429cMicrosoft.Office.DocumentManagement.Internal.DocIdHandlerDocument ID GeneratorSynchronous100041002Microsoft.Office.DocumentManagement, Version=14.0.0.0, Culture=neutral, PublicKeyToken=71e9bce111e9429cMicrosoft.Office.DocumentManagement.Internal.DocIdHandlerDocument ID GeneratorSynchronous100061003Microsoft.Office.DocumentManagement, Version=14.0.0.0, Culture=neutral, PublicKeyToken=71e9bce111e9429cMicrosoft.Office.Docu ՜.+,D՜.+,\x   < CAPITAL PLANNING AND MANAGEMENT UT MD ANDERSON CANCER CENTER@CC% BAS Operator Interfaces Title X<p _dlc_DocId_dlc_DocIdItemGuid_dlc_DocIdUrl Published Date to External SiteReady to PublishStatus