ࡱ> WYV_ 8bjbjzyzy MQ6b6b.?     8V$z<3(.@!$#3333333$4W7&3 $$$&3  4;32~(~(~($  3~($3~(~(VP0(1`2m$x1 2m3<31 84%8118 1H$$~($$$$$&3&3&$$$3$$$$8$$$$$$$$$ B : SECTION 26 22 14 high efficiency harmonic cancellation transformers GENERAL RELATED DOCUMENTS Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section. SUMMARY All transformers shall meet DOE 2016 requirements. This Section specifies the requirements for energy efficient dry-type harmonic cancellation transformers, rated 1000 V and less. All transformers shown on Drawings are single output on the secondary. Transformers shall be designed to treat all major harmonics produced by phase-neutral, phase-phase, and 3-phase six-pulse electronic equipment: 3rd, 5th, 7th, 9th, 15th, 17th and 19th in addition to other zero sequence currents. 3rd, 9th and 15th harmonic and other zero sequence currents shall be treated within the secondary windings of the transformer through flux cancellation and shall not be coupled into the primary winding. Trapping these currents in the primary delta winding, as is the case for the delta-wye transformer configuration, is not acceptable. 5th, 7th, 17th and 19th harmonics for single output transformers are treated by introducing the appropriate primary-to-secondary phase-shift in the transformer such that these currents subtract at the common bus with 5th, 7th, 17th and 19th harmonic currents produced by other similar harmonic current sources fed from the same bus. See Drawings for phase shift of each transformer. Fundamental current imbalance shall be reduced on the primary side of the transformer compared to the secondary side. Harmonic cancellation performance guarantee shall be provided by the manufacturer. Harmonic mitigation shall be obtained by electromagnetic means only. No capacitors or electronics shall be used. REFERENCE STANDARDS US Department of Energy, 10 CFR Part 431 Energy Efficiency Program for Certain Commercial and Industrial Equipment, Subpart K Distribution Transformers. US Department of Energy, 10 CFR Part 429 Certification, Compliance, and Enforcement for Consumer Products and Commercial and Industrial Equipment. NEMA ST-20 Dry-Type Transformer for General Applications. IEEE C57.110 Recommended Practice for establishing transformer capability when feeding non-sinusoidal load currents. The latest published edition of a reference shall be applicable to this Project unless identified by a specific edition date. All reference amendments adopted prior to the effective date of this Contract shall be applicable to this Project. All materials, installation and workmanship shall comply with the applicable requirements and standards addressed within all references. QUALITY ASSURANCE AND TESTING Listing and Labeling: Provide transformers specified in this Section that are listed by Underwriters Laboratories (UL), certified by CSA, bear the EPA ENERGY STAR logo. Transformers shall meet relevant NEMA, UL, CSA, NFPA, EPA Energy Star Program. Transformer, with characteristics and options specified, must deliver the energy savings required under the EPA ENERGY STAR program and bear the EPA ENERGY STAR logo. Minimum Linear Load Efficiency: NEMA TP-1 and EPA ENERGY STAR compliant; 97.5 percent for 30 kVA, 97.7 percent for 45kVA, 98.0 percent for 75 kVA, 98.2 percent for 112.5kVA, 98.3 percent for 150 kVA, 98.5 percent for 225 kVA, 98.6 percent for 300 kVA, 98.7 percent for 500 kVA. Non-linear Load Efficiency: Greater than 98 percent for all transformers 45kVA and above, greater than 97 percent for transformers 30kVA and smaller. Load per section Factory Test Reports above. Standard production tests to include: Applied potential test Induced voltage test Impedance voltage and load loss test Voltage ratio test No load and excitation current test Additional type test should be made available on request include: Short circuit test, BIL basic impulse insulation level test Partial discharge test Sound level test Temperature rise test SUBMITTALS Product Data: Include data on features, components, ratings and performance for each type of transformer specified. Include dimensioned plans, sections, and elevation views. Show minimum clearances and installed devices and features. Include outline and support point dimensions of enclosures and accessories, unit weight, voltage, kVA, and impedance ratings and characteristics. No load core loss, full load winding conductor loss, full load losses, efficiency at 25 percent, 50 percent, 75 percent and 100 percent rated loads, percent regulation with 80 percent and 100 percent power factor loads, sound level, tap configurations, insulation system type and rated temperature rise. Record Documents: Wiring Diagrams: Detail wiring and identify terminals for tap changing and connecting field-installed wiring. Product Certificates: Signed by manufacturer of transformers certifying that the products furnished comply with requirements, including harmonic performance guarantee. Factory Test Reports: Base data for electrical characteristics on actual laboratory tests of typical transformers for harmonic performance and energy efficiency. Testing to be conducted using three (3) single-phase 120V nonlinear load banks with personal computer harmonic profile (100 percent current THD) at 35 percent or more of transformer nameplate load level. Test results to be submitted at time of quotation to include transformer efficiency, change in voltage THD between transformer primary and secondary terminals, ratio of 3rd harmonic current in primary delta current profile compared to that in secondary phase current. Copies of manufacturers design and routine factory tests required by referenced standards, including results of zero sequence impedance and reactance tests. DELIVERY, STORAGE and HANDLING Transport, handle, store and protect products. Deliver transformers individually wrapped for protection and mounted on shipping skids. Store in a clean, dry space. Maintain factory wrapping or provide an additional heavy canvas or plastic cover to protect units from dirt, water, construction debris, and traffic. Do not stack transformers. Temporary Heating: Apply temporary heat according to manufacturers written instructions within the enclosure of each ventilated-type unit throughout periods during which equipment is not energized and is not in a space that is continuously under normal control of temperature and humidity. Transformers shall not be used as work tables, scaffolds or ladders. WARRANTY Provide ten (10) year pro-rated warranty against defects in materials and workmanship, with limited liability. PRODUCTS GENERAL All materials shall meet or exceed all applicable referenced standards, federal, state and local requirements, and conform to codes and ordinances of authorities having jurisdiction. MANUFACTURERS Manufacturer must be a US Environmental Protection Agency (EPA) ENERGY STAR Partner. Manufacturers: Powersmiths International Corp. Power Quality International, Inc. CONSTRUCTION Exceed minimum efficiency requirements of US Department of Energy, 10 CFR Part 431 (DOE 2016), by complying with the table of Maximum No Load Losses, efficiency requirements at 35% & 50% linear load, as well as efficiency at 50% load under a K-13 load profile. Testing backed by ISO 17025 efficiency test lab. Description: Factory-assembled and tested, convection air-cooled units of types specified. Frequency: 60 Hz. System Voltage: 480V, 3-phase primary to 208/120V, 3-phase, 4-wire secondary. Core: Grain-oriented, non-aging silicon steel, 3-leg, common core. Coils: Continuous copper windings without splices, except for taps. Internal Coil Connections: Brazed or pressure type. Primary Winding: One coil per phase and per core leg; 3-phase, 3-wire input. Secondary Winding: Multiple coils per phase and per leg; one 3-phase, 4-wire output for all transformers. Insulation class: 220-degree C. Rated Operating Temperature Rise: 150 degrees C above 40 degrees C ambient for 0-degree phase shift units and 130 degrees C above 40 degrees C ambient for 30 degree phase shift units. Taps: Full-capacity taps in primary side windings are as follows: 45kV and above: Four 2.5-percent taps, 2 above and 2 below rated voltage. Impedance Positive and negative sequence: 2.5 4.0 percent (up to 75kVA), 3.0 4.8 percent (112.5 300 kVA). Zero sequence impedance and reactance: Less than 0.95 percent and 0.3 percent respectively. Efficiency: Greater than 98 percent per EPA ENERGY STAR energy savings program requirement. Enclosure Finish: Epoxy powder coating. Enclosure Color: Manufacturers standard. Enclosure type: Indoor, ventilated, drip proof, NEMA-1. Other enclosure requirements: provide hinge doors for transformer winding inspection. Sound Levels: Per NEMA ST 20 standard sound levels when factory tested according to IEEE C57.12.91. 10-50kVA: 45 dB, 51-150kVA: 50 dB, 151-300 kVA: 55 dB. Varnishing: The manufacturing process shall incorporate epoxy vacuum impregnation; both primary and secondary windings. Electrostatic Shielding: Each winding is independently single shielded with a full-width copper electrostatic shield. Neutral conductor rating shall be 200 percent of phase rating. Ratings as scheduled, capable of operating at 100 percent load continuously at an ambient temperature of 40 degrees C under full harmonic load profile. Lugs shall not be provided with the transformer due to the variety of installation scenarios, such as single or multiple conductors per phase. Terminal strips: Copper, with holes pre-drilled for 3/8-inch hardware. Integrated Rotatable IR-Port- Safe & easy access for thermal scans without the Arc Flash risk and time of opening a live transformer. EXECUTION PREPARATION Examine the areas and conditions under which dry type transformers are to be installed and notify the Contractor in writing of conditions detrimental to the proper and timely completion of the Work. Do not proceed with the Work until unsatisfactory conditions have been corrected. INSTALLATION Installation shall meet or exceed all applicable federal, state and local requirements, referenced standards and conform to codes and ordinances of authorities having jurisdiction. All installation shall be in accordance with manufacturers published recommendations. Install transformers as indicated, in accordance with the applicable requirements of the NEC and the National Electrical Contractors Associations Standard of Installation. Install floor-mounted transformers on concrete housekeeping pads with vibration isolating pads suitable for isolating the transformer noise from the building structure in accordance with Section 26 01 00, Basic Electrical Requirements. Maintain a minimum of 6 inches free air space between enclosure and walls. For floor and trapeze transformer installations, use one pad type Korfund Elasto-Grip waffle at each corner of the transformer, sized for load of 50 pounds per square inch. For wall hung transformer installations (15kVA and less), use spring type Korfund Series P. Provide sound pads at each corner of the transformer sized for inch deflection. Securely anchor wall-mounting brackets to wall to provide adequate support. If and when applicable, suspend transformers (45 kVA and less) from structure by means of trapeze hangers constructed of -inch galvanized all-thread rods and metal framing channels. Make double-nut connections between rods and channels. Locate to provide adequate ventilation and accessibility. Check for damage and tight connections prior to energizing transformer. Verify adjustment of coil shipping anchor bolts prior to energizing. Measure primary and secondary voltages and make appropriate tap adjustments. Set transformer plumb and level. Use flexible conduit, two (2) feet minimum length, for connections to transformer case. Make conduit connections to side panel of enclosure. Transformer nameplate should include the following: Name/ Fed From / Feeds. END OF SECTION 26 22 14   MD ANDERSON Project No. XXXXXX MD ANDERSON PROJECT NAME A/E Name Issue Description A/E Project No. Month 00, 0000 鶹ӳ high efficiency harmonic cancellation transformers MD Anderson Cancer Center 26 22 14 MS 20190301  PAGE 1 OF  NUMPAGES 6 C]^f' S T Z [ d e # ' @ D a q ( * , - / 3 5 >         y '(45@AIKpٵٵٱٱٱh0hl%hrh H*h hrhRH*hRhrh6H*h6hE$ h~uh!Sh3 h.\hKuhKuh8hi+FDL^' ' (bUQoi'gdrgdtgdqgdJgd4#LgdO&'(abADOPbnohi*+?@dewx23CDYZs% \dwXw6!?!!! h0h0hJ h6h;3 hOh;3 hOh-Rh;3 h6h6h-Rh0h3 hOh;h; h4#Lhi hrhihhi hrh h.\hKuhKuh69+@ex3DZesQ%=Xgd6gd6$$gd.\gd.\gdr gd;3oe'gd4#L gd;3oe' gd;3oe'gdrXw 6!?!!!!v"""" #,#:#p$$$.%r%%gd@vgd0gd6gd0gd( gdRgdtgdqgd4#L!v""""" # #,#9#:#o$p$%%N&O&&&&&' '''?'@'R'U'D(L(e(m(((((((())))*&-'-I-Q-\----_.i.....///,00011J2i22233\3^3h h.\hKuh3hJhmh:wh(hUBh: h4#Lhe hrheh@vh0h6hKuJ%%:&&&'(((;)d)))**7+++,-\----/ //gd4#Lgdrgd( /,002234t555p666666666666666gd.\ `gd( gd( gdRgd4#Lgd@vgdtgdq^3a3b333546474;4555566o6p66666666677p7q7r7s7t77777777777777777 8 8 8 88888888ѽѽͽѲѲѡjh.\Uhi+mHnHujhKnh.\Uh.\h.\h.\;hhi+ hKnh.\hsK"jhsK"UhKuh( h6hh4#LhJh@v:66666666666666666666666647P7o7p7q7gd.\q7r7s7t777 888888888gd.\gd.\gd.\K....()()))()000?P&P/R 8$:p.\BP/ =!"#8$% Dp!s002 0@P`p2( 0@P`p 0@P`p 0@P`p 0@P`p 0@P`p 0@P`p8XV~ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@ 0@_HmH nH sH tH @`@ .\NormalOJQJ_HmH sH tH ZZ  Heading 1$ <@&^ ;CJKH \^JaJ RR  Heading 2$ P 1$@&^  5;CJXX  Heading 3$ h!  1$@&^ 5;mH sH DA D .\Default Paragraph FontViV  Table Normal :V 44 la (k (.\No List 0O0 .\EOS $a$5H`H .\0Header  $OJQJ_HmH sH tH 6/6 .\0 Header CharOJQJ: @": .\0Footer  $B1$\]6/16 .\0 Footer CharOJQJFORF .\PRT $$ & F *$@&a$5;HObH .\ART$$ & F @&a$ ;\]^J@Ob@ .\PR1$$ & F *$@&a$^J4/q4 ( PR1 Char OJQJ^J@O@ .\PR2$$ & F *$@&a$^J@O@ .\PR3$$ & F *$@&a$^J4/4 .\PR3 Char OJQJ^J@@ .\PR4$$ & F *$@&a$^J@@ .\PR5$$ & F *$@&a$^J2O2 OCMT $1$5;J JO0RevisionOJQJ\]_HmH sH tH 4B4 .\SCT *$ 5;^JBB .\ SPEC NOTE x5B*\phPK![Content_Types].xmlN0EH-J@%ǎǢ|ș$زULTB l,3;rØJB+$G]7O٭Vc:E3v@P~Ds |w< 0&"':<>A!^38"%X%/6q78 !#$&'!#(46A!t@ @H 0(  0(  B S  ?< _Hlk446890 _Hlk446891 _Hlk447214 _Hlk447215 _Hlk447605 _Hlk447606 _Hlk448082 _Hlk448083 _Hlk449066 _Hlk449067 _Hlk449381 _Hlk449382 _Hlk449571 _Hlk449572 _Hlk449859 _Hlk449860 _Hlk450078 _Hlk450079 _Hlk450272 _Hlk450273 _Hlk450793 _Hlk450794 _Hlk451149 _Hlk451150 _Hlk451408 _Hlk451409 _Hlk451576 _Hlk451577 _Hlk451801 _Hlk451802 _Hlk451951 _Hlk451952 _Hlk452108 _Hlk452109 _Hlk452263 _Hlk452264 _Hlk452441 _Hlk452442 _Hlk452613 _Hlk452614 _Hlk506465 _Hlk506466 _Hlk506493 _Hlk506494 _Hlk506886 _Hlk506887 _Hlk506946 _Hlk506947 _Hlk507318 _Hlk507319 _Hlk508067 _Hlk508068 _Hlk508099 _Hlk508100 _Hlk512259 _Hlk512260 _Hlk512823 _Hlk512824 _Hlk513067 _Hlk513068............................................................0  !"#$%&'()*+,-./0123456789:;o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/o/0""U*\*]*c* ++...........//00P S .........../ 000333'DDaa,,(:p!!!!"I%I%Q%[%%++n.n.o........s/t//// 00000'DDaa,,(Y:p!!!"I%Q%[%%++n.n.o.................p/q/s/t//// 00000 pSlV$+wRr* ^`o(hH PART -  ^`o(hH SCHEDULE  -  ^`o(hHPRODUCT DATA SHEET  -  `h^``o(hH. 8h^8`o(hH. h^`o(hH. h^`o(hH. ph^p`o(hH)  h^ `o(hH)@@^@`^`.0^`0.``^``.^`)^`) ^` ...... `^``....... 00^0`........ `^``o(hH PART -  ^`o(hH ^`o(hH ``^``o(hH. ``^``o(hH. ^`o(hH. ^`o(hH.   ^ `o(hH) ` ` ^` `o(hH)  SlwRrR<0LK>W ( 1* qRst-J8%E$ ;*"sK"i+P.037zAV DJ4#LR-R!S3hKu~u:wW rl}3OUB=mC~ifj;`pr6Jm@R:`-%;.\(+B;3l%e] }h@v}6^XtrA#..@00@Unknown Ramann ManthaG*Cx Times New Roman5Symbol3. *Cx ArialA$BCambria Math"9A)htt-h'U'U%)P24..3q)PHP ?82xx 2High Efficiency Harmonic Cancellation TransformersDOSpainFitzgerald,Richard W   Oh+'0\    $ 0<DLT4High Efficiency Harmonic Cancellation TransformersDOSpainALTERATION OF THIS OFFICIAL DOCUMENT IS PROHIBITED WITHOUT EXPRESS WRITTEN PERMISSION BY OFFICE OF CAPITAL PLANNING AND MANAGEMENT AT UT MD ANDERSON CANCER CENTER.NormalFitzgerald,Richard W2Microsoft Office Word@@"(7-@Fm@Fm'Status CSI Division SZWXXFYDWACR-487-737%2fd50153-c429-4adf-ba20-487d3800784cthttp://fm/groups/cmentManagement.Internal.DocIdHandler/metadata/longProperties"/> <  !"#$%&'(*+,-./0123456789:;<=>?@ABCDEGHIJKLMoQRSTU]X[u\O^_`abcdefghijklmnvwxyzNRoot Entry F`foZ1Table)38WordDocumentMQSummaryInformation(FDocumentSummaryInformation8,\CompObjrMsoDataStore `fo`foNSLD0OUQ==2`fo`fo  !"#$%&'()*+<-./0123456789:;B=?@ACDEFG  F Microsoft Word 97-2003 Document MSWordDocWord.Document.89q Item  Px.Properties0O1YJDECA3ZHOQ==2 `fo`foItem  Properties1OSEA3B05A==2`fo`foItem  Properties/xsd:simpleType> This value indicates the number of saves or revisions. The application is responsible for updating this value after each revision. 0"> ds:itemID="{9CE1BFDD-BDEB-4F48-808B-376F9E605A7C}" xmlDocumentLibraryFormDocumentLibraryFormDocumentLibraryForm">Document ID Generat Token=71e9bce111e9429cMicrosoft.OfficDocument ID GeneratorSynchronous100011000Microsoft.Office.DocumentManagement, Version=14.0.0.0, Culture=neutral, PublicKeyToken=71e9bce111e9429cMicrosoft.Office.DocumentManagement.Internal.DocIdHandlerDocument ID GeneratorSynchronous100021001Microsoft.Office.DocumentManagement, Version=14.0.0.0, Culture=neutral, PublicKeyToken=71e9bce111e9429cMicrosoft.Office.DocumentManagement.Internal.DocIdHandlerDocument ID GeneratorSynchronous100041002Microsoft.Office.DocumentManagement, Version=14.0.0.0, Culture=neutral, PublicKeyToken=71e9bce111e9429cMicrosoft.Office.DocumentManagement.Internal.DocIdHandlerDocument ID GeneratorSynchronous100061003Microsoft.Office.DocumentManagement, Version=14.0.0.0, Culture=neutral, PublicKeyToken=71e9bce111e9429cMicrosoft.Office.Docu ՜.+,D՜.+,xx   W CAPITAL PLANNING AND MANAGEMENT UT MD ANDERSON CANCER CENTER@U. 3High Efficiency Harmonic Cancellation Transformers Title X<p _dlc_DocId_dlc_DocIdItemGuid_dlc_DocIdUrl Published Date to External SiteReady to Publish